Choosing the Right Fuses: Transformers 101

April 23, 2024

Transformers 101: Choosing the Right Fuses

Types of Fuses

Fuses come with a variety of options, each type designed for a specific application. While these fuses may share the same current rating, they have different clearing curves which means some can handle large inrush currents for up to 10 seconds, while some blow right away.

Selection Criteria

When Selecting a fuse, you must consider the following:
  1. Current (Amps)
  2. Voltage
  3. Available Fault Current (Generally measured in kA)
  4. Application (What are you protecting?)

Choosing the Right Size for a Transformer

Determine where you will fuse primary only or primary and secondary and calculate the primary current (Amps).

Use the table below to guide you further:

Primary Fuse

Primary AmpsMax Primary Fuse % Rating
9 or more125*
2 to less than 9167
less than 2300

Primary & Secondary Fuse

Secondary AmpsMax Primary Fuse % Rating
PrimarySecondary
9 or more250125*
less than 9250167
*If 125% does not correspond to a standard ampere rating, the next higher standard rating shall be permitted.

Placement of Fuses

  • Primary Fuse (Input)
    • essential to protect against short circuit and overloads.
  • Secondary Fuse (Output–optional)
    • safeguards against overloading the transformer.

Consider the Starting Current

Primary fuses must be able to handle the high inrush current of a transformer. This can be as much as 30 x calculated current for .01 seconds. A time delay dual-element fuse is recommended.

Check this fuse selection table for control and 3-phase transformer:

vancoelectrical.com/fuse-table

Example

Let’s suppose we have a transformer with the following specifications:

  • Transformer Rating: 45 kVA
  • Primary Voltage: 600V (3-phase)
  • Secondary Voltage: 208/120V (3-phase)

Calculate Primary Current:

Primary Current (A) = kVA x 1000 / √3 x Primary Voltage (V)

Primary Current (A) = 45 kVA x 1000 / √3 x 600 (V)

Primary Current (A) ≈ 45000 /  √3 x 600 (V) ≈ 45000/1039.2 ≈ 43.35 A

Choose Fuse Rating (125% of the calculated primary current)

Fuse Rating (A) = 1.25 x Primary Current (A)

Fuse Rating (A) = 1.25 x 43.35 A

Fuse Rating (A) ≈ 1.25 x 43.35 A ≈ 54.19 A

So, we’d select a fuse close to a rating of 54.19 A, which is 60 A.

Source

More Information

Vanco Electrical Supply Ltd.

Related Story

Discover MTE Through Vanco’s Unmatched Expertise and Service

At Vanco Electrical Supplies, their commitment is not just about providing electrical products; it’s about cultivating partnerships and seizing opportunities to better serve their clients. Founded by Walter Wiebe and Dave Nicoll, their roots in Markham, Ontario were sown with a commitment to offer technically competent representation to emerging manufacturers overlooked by the market.

Related Articles



Editor’s Pick: Featured Article

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s scalable engineering software, u-control 2000, adapts individually to your requirements. And, the u-control is powerful, compact and fully compatible with Weidmüller’s I/O system u-remote. This article looks at what makes u-control the heart of your automation.

Programmable logic controllers (PLCs) are one of the main components of any automated system. A typical control system has inputs, outputs, controllers (i.e., PLCs), and some type of human interaction with the system, a human machine interface (HMI), for example.

Read More



Latest Articles

  • NVIDIA 800 VDC Architecture Will Power the Next Generation of AI Factories

    November 4, 2025 By Mathias Blake, Martin Hsu, Ivan Goldwasser, Harry Petty and Jared Huntington The exponential growth of AI workloads is increasing data centre power demands. Traditional 54 V in-rack power distribution, designed for kilowatt (KW)-scale racks, isn’t designed to support the megawatt (MW)-scale racks coming soon to modern AI factories.  NVIDIA is leading the transition to 800 VDC data… Read More…

  • Efficient Power Monitoring at the Edge: Moxa’s DCI Solutions for Data Centres

    November 4, 2025 As data centres grow in higher densities to support AI-enabled workloads and more complicated operations, keeping the Power Usage Effectiveness (PUE) at optimum is critical at this time. Downtime is never acceptable. Also, without being able to see electrical systems in real-time, such as substations, UPS, switchgear, and HVAC, failures will take… Read More…